Mô tả

Industrial UPS | 100kVA / 80kW | 3 Phase | 480V Wye Systems | Support VRLA battery or LiFePO4 battery

In an automated manufacturing environment, even a brief power interruption poses serious risks. It can result in production downtime, equipment damage, data loss, and significant financial losses. Factory equipment includes CNC machines, robotic production lines, PLC control systems, automated packaging equipment, and industrial servers. These systems require a continuous and stable power supply to maintain operational efficiency.

Prostar ET100K HV stable power 100kva ups system is specifically designed to provide reliable backup power for industrial machinery and critical factory operations. With advanced online double conversion technology, this online UPS system continuously converts incoming AC power to DC and back to clean AC. This means zero transfer time, zero output distortion, and complete isolation from grid noise, sags, surges, and frequency drift. For facilities that demand reliable backup power for industrial machinery, this architecture is non-negotiable.

Table of Contents

Typical Factory Power Challenges

Manufacturing facilities often face various power quality issues, including:

Voltage Sags and Surges

Heavy industrial loads frequently cause voltage instability. Motors, compressors, and welding equipment can create sudden voltage drops that affect sensitive electronic systems.

Unexpected Power Outages

Grid failures, transformer faults, and severe weather conditions can lead to unexpected production stoppages.

Harmonic Distortion

Modern industrial equipment generates harmonics that can negatively impact power quality and reduce equipment lifespan.

Increasing Automation Requirements

As factories adopt Industry 4.0 technologies, stable power becomes increasingly important for networked equipment, industrial computers, and automated control systems.

A high-performance 100kVA UPS system helps eliminate these risks and ensures continuous production.

Prostar ET100K HV 100kVA UPS system for manufacturing plant backup

Why Choose 100kVA UPS System for Your Factory?

Prostar  ET100K HV is a premium 100kVA UPS system engineered for demanding industrial environments.

Online Double Conversion Protection

The system continuously converts incoming AC power into DC and then back into clean AC power. This online double conversion UPS architecture completely isolates connected loads from utility power disturbances.

Your factory can get:

  • Zero transfer time

  • Pure sine wave output

  • Stable voltage regulation

  • Frequency stabilization

  • Protection from power anomalies

Three-Phase Power Architecture

The ET100K HV supports 480V three phase UPS system applications, making it suitable for large industrial facilities and heavy-duty equipment.

Wide Input Voltage and Frequency Range

Industrial power grids often experience voltage fluctuations and frequency instability, especially in manufacturing facilities with heavy electrical loads.

The ET100K HV 100kVA UPS system supports a wide input voltage range and frequency range, allowing the UPS to continue operating normally without unnecessarily switching to battery mode. This feature significantly extends battery life while improving overall system reliability.

Benefits are including:

  • Reduced battery discharge cycles

  • Enhanced power availability

  • Better adaptation to unstable utility grids

  • Lower battery maintenance costs

Prostar 3 phase online double conversion UPS working principle diagram

Convenient Bottom Cable Entry Design

The ET100K HV adopts a bottom cable entry structure for simplified installation and maintenance.

This design is particularly beneficial in industrial environments where power cables are routed through cable trenches or raised floors.

Advantages:

  • Cleaner cable management

  • Faster installation

  • Improved maintenance accessibility

  • Enhanced safety and professional appearance

Superior Overload Capability

Factory equipment often experiences temporary load surges during startup, motor acceleration, or process switching.

The 480V three phase UPS system provides exceptional overload performance to maintain stable operation under demanding conditions.

Load Condition

UPS Performance

≤ 105% Load

Continuous operation

105% – 125% Load

Transfers to bypass after 10 minutes

125% – 150% Load

Transfers to bypass after 1 minute

This super overload capacity protects critical production equipment while preventing unnecessary system shutdowns.

Industrial benefits:

  • Supports motor starting currents

  • Handles temporary production load peaks

  • Improves overall system stability

  • Reduces risk of unexpected downtime

Parallel Redundancy Capability

As manufacturing operations grow, power requirements often increase.

The UPS system for manufacturing facilities supports parallel-redundant operation with up to 8 units connected in parallel, providing exceptional scalability and system availability.

Capacity Expansion

Users can gradually increase UPS capacity without replacing existing equipment.

N+1 Redundancy

Additional UPS modules can be installed to create fault-tolerant systems, ensuring continuous operation even if one UPS unit becomes unavailable.

Increased Reliability

Parallel redundancy minimizes the risk of production interruptions caused by power system failures.

Generator Compatibility

The system works seamlessly with diesel generators, providing stable power during extended utility outages.

How the 100kVA UPS System Protects Factory Equipment

Utility Failure

When utility power fails, the 100kVA UPS system instantly draws energy from the battery bank without any interruption to connected equipment.

Voltage Fluctuations

The UPS continuously regulates output power, ensuring sensitive equipment receives stable voltage regardless of utility conditions.

Harmonic Disturbances

Advanced filtering technology minimizes harmonic distortion and delivers clean power to critical loads.

Generator Operation

The UPS conditions generator output power and eliminates fluctuations before supplying power to protected equipment.

100kVA UPS system protecting factory equipment and industrial automation systems

Technical Specification

Model

ET100K HV

Capacity

100KVA/80KW

Topology

Double conversion online

Input Nominal Voltage

480Vac, 3P+N+PE

Input Voltage Range

384 – 576Vac

Input Rated Frequency

50Hz/60Hz (Automatically)

THDi

< 3% at full load

Output Rated Voltage

480Vac, customized 208Vac/220Vac ± 1%

Frequency

Mains mode: synchronized with bypass input, 50Hz/60Hz±0.01%(By Battery)

THDu

<2% at 100% liner load, <5% at 100% non-liner load

Overload Capacity

105-110%: 60 mins, 110-125%: 10 mins, 125-150%: 1 min, >150%: 200ms

Crest Factor

3:1

Wave Form

Pure sine wave

Transfer Time

0ms

Efficiency at full load(AC-AC)

> 93%

Efficiency at ECO Mode

> 98%

Battery Type

Support VRLA battery or LiFePO4 battery option

Battery Voltage

360Vdc default, 336-384VDC

Enclosure

IP31

Parallel Number

Up to 8 units

Cooling Method

Forced air cooling (fans)

Display

7-inch color LCD touch screen

Operating Temperature

0℃ to 40℃

Communication

RS232, RS485, USB, Dry contact, EPO

Alarm Code

Code

Alarm Message

Possible Causes

Recommended Service Action

1

Mains abnormality

Input power failure

Check mains power supply

4

Bypass abnormality

Bypass voltage / frequency out of range, wiring issue, exceed the number of bypass switching

Check bypass input voltage, frequency, and wiring. Turn off UPS and re-start again.

8

Abnormal mains voltage

Mains voltage out of range

Stabilize input voltage

9

Abnormal mains frequency

Frequency instability

Check generator or grid quality

10

Reversal of phase sequence of main input

Phase wiring error

Correct main input phase sequence

11

Over-voltage of Phase A of AC input

Phase A voltage too high

Check Phase A input

12

Under-voltage of Phase A of AC input

Phase A voltage too low

Check Phase A input

13

Over-voltage of Phase B of AC input

Phase B voltage too high

Check Phase B input

14

Under-voltage of Phase B of AC input

Phase B voltage too low

Check Phase B input

15

Over-voltage of Phase C of AC input

Phase C voltage too high

Check Phase C input

16

Under-voltage of Phase C of AC input

Phase C voltage too low

Check Phase C input

30

Abnormal bypass voltage

Over/under bypass voltage

Measure bypass voltage and correct power source

32

Bypass overload

Load exceeds bypass capacity

Reduce load and check load distribution

33

Bypass overload delay timeout

Long-term overload on bypass

Reduce load and restart UPS

34

Bypass frequency over-tracking

Unstable bypass frequency

Check bypass power quality

29

Bypass phase sequence reversal

Phase sequence incorrect

Correct bypass phase sequence

35

Shutdown due to bypass abnormality

Severe bypass abnormality

Inspect bypass input and restart

50

Fan failure

Fan blocked or damaged

Replace fan and check airflow

UPS Troubleshooting

Code 32 & 33 – Bypass Overload / Timeout

These indicate the load has exceeded the KVA rating of the SCRs (Static Switches).

Action:

  • Check the Crest Factor of the load. High non-linear loads (like servers) can trigger peak current alarms even if the RMS current seems normal.

  • Check for “Load Unbalance.” In 3-phase systems, if Phase A is at 110%and Phases B/C are at 20%, the UPS will still trigger an overload. Redistribute the load across phases.

Code 29 – Bypass Phase Sequence Reversal

The UPS logic compares the phase angle of the Inverter vs. the Bypass. If they are 120° out of sync, the “Static Switch” cannot transfer without damaging the load.

Action:

  • Use a Phase Rotation Meter at the Bypass Input Terminals.

  • Ensure rotation is Clockwise (L1 \ L2 \ L3).

  • Check the “Sync” signal on the control board; if the phase is physically correct but the error persists, the sensing transformer or control board is faulty.

Code 10 – Reversal of Phase Sequence of Main Input

The Rectifier (SCR or IGBT based) synchronization depends on the “Zero Crossing” of the input waves. Wrong sequence prevents the Rectifier from firing correctly.

Action:

  • Measure VL1-L2, VL2-L3, andVL3-L1. All should be approximately equal (e.g., 380V/400V/415V).

  • Swap any two input cables (e.g., L1 and L2) at the Main Input Breaker to correct rotation.

Code 11 – 16 – Phase Specific Over/Under Voltage

If only one phase (e.g., Phase A) reports an error, it is likely a local distribution issue or a “Neutral Drift.”

Action:

  • Check the Neutral (N):In a 3-phase 4-wire system, a loose Neutral can cause phase voltages to “float.” Measure VL-N for all phases.

  • Input Fuse Check:If a phase reports “Under-voltage” (0V), check the high-speed input fuses located before the Rectifier.

  • Sensing Board:If your external multi-meter shows 230V but the UPS LCD shows 160V, replace the Voltage Sampling Board.

Code 50 – Fan Failure

Fans stop and alarm.

Action:

  • Physical Inspection:Power off the fan and check for any foreign objects obstructing the blades. Manually rotate the fan to check for smooth rotation.

  • Direct Measurement:Measure the AC supply to the fan (usually 220VAC). If there is no voltage, check the motherboard power supply fuse.

  • Thermal Correlation:Check if Code 53 Heatsink Over-temp If not, the sensor might be the only issue. If yes, the airflow is physically blocked.

  • Feedback Signal:If the fan rotates normally but the error message persists, the third wire of the fan (speed detection wire) may be broken or the control board interface may be faulty.

FAQ

How many amps is 100 kVA 3 phase?

Due to 100kVA with 0.8 output power factor, the 480V three phase 100kVA UPS system output current is about 97 amps.

What is 100 kVA in kW?

Prostar ET100K HV scalable 100kVA UPS system with 0.8 output power factor, it gives out 80kW.

Is the ET100K HV 100kVA UPS system suitable for manufacturing plants?

Yes. It is specifically designed as an industrial UPS for manufacturing plants where stable and uninterrupted power is essential.

Can this industrial UPS system operate with a generator?

Yes. The three phase UPS system supports generator integration and ensures clean power delivery during prolonged outages.

Is this industrial UPS parallel redundancy available?

Yes. Multiple ET100K HV 100kVA UPS system can operate in parallel to provide redundancy or increased capacity.